Control valve symbols on a P&ID are read by starting with the basic bow-tie body shape, then checking the internal marker for valve type, the tag number for identification, and the actuator symbol for control method. Together, these elements tell you what the valve does, how it operates, and where it fits into the overall process.
A Piping and Instrumentation Diagram (P&ID) is the master reference drawing for an industrial process plant. Control valves shown on this diagram are the final mechanical elements that regulate pressure, flow, temperature, and liquid level.
Engineers use the P&ID to design the plant before construction begins. Once approved, the same diagram guides purchasing teams, equipment vendors, and the crews who install everything on site.
Misreading a single symbol can cause real problems. A line could be overpressurized, or flow could reverse unexpectedly when it shouldn’t. This is why PID valve symbols follow standardized conventions instead of varying by company or engineer.
Note: Plumbing plans and full P&ID drawings use overlapping but distinct symbol sets. This guide on plumbing valve symbols breaks down where the two diverge.
Every standard valve symbol starts with two triangles pointing toward each other, known as a “bow-tie.” This shape represents the physical valve body sitting in the pipeline.
Engineers identify each valve’s specific role using alphanumeric tags defined by ANSI/ISA-5.1, the main industry standard for instrumentation symbols. A few common examples:
Gate valves carry their own tagging quirks worth knowing, especially around sizing notes. We cover this in more depth in how to read the gate valve symbol in P&ID.
Notes near the symbol often include sizing and rating data. A note like 2″ 300 RF PB means the valve is 2 inches in diameter, rated to ANSI Class 300, has a raised-face connection, and uses a piston-balanced trim design. This kind of shorthand lets engineers pack a full spec sheet’s worth of detail into a few characters on the drawing.
The internal design of a valve determines how it controls fluid movement, so P&IDs use distinct internal markers for each type:
A valve only becomes a “control valve” once an actuator is attached to operate it automatically. On a P&ID, the actuator is drawn as a shape connected to the top of the valve stem:
Two accessories often appear alongside the actuator symbol:
Fail-safe behavior is marked with an arrow or letter code. An upward arrow or “FO” means the valve fails open, while a downward arrow or “FC” means it fails closed. This tells operators exactly how the valve will behave if it loses power or air supply.
To trace a full control loop, follow the signal path from the field sensor through the controller to the valve. A typical loop includes a transmitter, such as TT for temperature, a controller that processes the signal, and the actuated valve that responds to it. In many plants, this controller is part of a larger DCS (Distributed Control System) or PLC (Programmable Logic Controller) that manages dozens of loops at once.
Two line types show how these components communicate:
By following these lines from the transmitter to the final valve, you can tell whether a rising measurement will cause the valve to open further or close down. This single skill turns a dense, intimidating drawing into a clear story of cause and effect across the entire process.
Where Plug Valves Fit in P&ID Systems
Plug valves are quarter-turn, high-integrity isolation devices chosen over ball valves for high-pressure, slurry-heavy, or highly corrosive process streams, thanks to their cavity-free, self-cleaning seating surfaces. On a standard ANSI/ISA-5.1 P&ID drawing, a plug valve is distinguished from a ball valve by a rhombus (diamond) shape, or an explicit internal rectangle inside the bow-tie body, rather than an open circle.
B2B engineers should account for three technical layers when reviewing plug valves on a P&ID: